T Y P I C A L   E X A M P L E

>

Fire & Hydrocarbon Gas Detection System
Client: Oil & Natural Gas Corporation Ltd. (ONGC)
Place: Uran

We have recently implemented a turnkey project covering supply, installation, integration and commissioning of Fire And Gas Detection System for oil and gas processing complex of Oil & Natural Gas Corporation Ltd., at Uran. The project was completed a month ahead of schedule. We supplied these systems with technical backup from M/s. Detector Electronics Corporation, USA. We imported major equipments from Detector Electronics Corporation. The control system design & Engg was done by Detector Electronics and the site engg, supply of indigenous items/equipments etc was carried out by us to put together a complete system, as per clients need. Our specialized team of Engineers installed and integrated this system to the existing DCS system of our client. These services were again part of the turnkey contract. The site acceptance of the Project was completed on 6th August 2002.

The technical brief of the project: -

System Overview
The Fire & Gas System consist of the following components:

  • Infrared Gas Sensor/Detectors
  • Digital Communication Units
  • Initiating Device Circuit module
  • Control Units with necessary software.
  • Local Input/Output Unit
  • Signal Audible Modules
  • Audible/Visual Devices
  • Cables / Trays / Ducts & all other required hardware.

Scope of work

The turn key responsibility for the project involved Design & Engineering, Supply, Erection, Integration & commissioning:

A- Engineering:
-
To design Fire & Gas detection System based on fail safe philosophy and all other referred applicable standards.
 
-
Finalise Optimum Location of Fire & Gas detectors.
 
-
Location of Junction boxes, power supplies, beacons, hooters etc.
 
-
Design & Engineering of trays / ducts and routing.
 
-
Design & Engineering for Integration with existing Gas detection system, outputs required to operate existing Sprinkler system, serial communication with existing DCS systems.
 
-
Design & engineering of custom graphics, reports, device layouts, etc.
 
-
Preparation of all documents, drawings as required.
 
 
B- Supply:
-
Supply of Addressable Fire and Gas Detection panel with Control Unit Hardware for Monitoring, Controlling, Data acquisition, Logic capabilities, alarm, annunciation, Alarm and Event printing, integration with existing DCS/PLC s.
 
-
Supply of Operator Interface station, Operating System software, Configuration Software, Engineering software, Graphic software, Printers and the required furniture.
 
-
Supply of 180 Nos. of IR Type Hydrocarbon Gas detectors/ Transmitters & 16 Nos. UV /IR Type Fire Detectors with Communication Modules.
 
-
Supply of all required cables in required quantities.
 
-
Supply of cables trays, cable ducts, conduits, supports, brackets, etc required for laying of cables.
 
-
Supply of instrument mounting accessories like pipe stanchions, brackets, structural supports, cable glands, etc.
 
-
Supply of Junction Boxes, Cabinets, MCT Blocks, circuit Breakers, Hooters, Beacons, Relays etc
 
-
Supply of one lot of testing and calibration equipment.
 
-
Supply of commissioning spares and consumables.
 
-
Supply of Recommended spares & consumables for 2 years operation.
 
-
Supply of ten sets of hard copy documentation and 2 sets of softcopy documentation as required.
 
-
Supply of any other Material not listed above but necessary for completion of the job.
 
 
C- Installation:
-
Installation of stanchions for all the Gas Detectors Transmitters, Fire Detectors/Transmitters , Junction boxes, Beacons, Hooters, etc. including all the necessary civil job.
 
-
Installation of new tray/duct/supports for laying of new cables.
 
-
Installation of Standalone Panels, Gas Detectors/ Transmitters, Fire Detectors/Transmitters, Power Supplies, Beacons, Hooters, Junction Boxes, etc.
 
-
Laying of power supply cables, communication cables, signal cable, control cable, earthing cable and all other necessary cables.
 
-
Glanding, termination of all the cables.
 
-
Installation of all the software.
 
-
Installation of permanent Tag Plates on all devices in the field and the panel. Installation of any other sensor, device, hardware not mentioned specifically but required for completion of the job.
 
 
D- Commissioning:
-
Calibration of all the devices.
 
-
Loop checking & interlock checking of all the loops from sensors /transmitters to Gas Detector Panel and DCS.
 
-
Testing, Debugging & Commissioning of the Addressable Fire and Gas Detection System Control Panel.
 
-
Testing & Commissioning of the communication link between Fire and Gas Detection System and DCS System.
 
-
Site/Field acceptance test after commissioning of the total system.
 
 
E- Support Services:
-
Training; conduct a course in device maintenance, hardware maintenance, software maintenance and diagnostics of the system.
 
-
Providing warrantee services for a period of 1 year from date of commissioning.
 
 

System Design and Functions

The Fire and Gas Detection System as installed consists of a main control panel, operator interface station, IR hydrocarbon gas detectors (180 Nos.), UV/IR fire detectors (16 Nos.), and audible/visual alarms.. In the event of an alarm by the fire and gas detectors or from the existing fire and gas systems (As a part of system integration), the system sounds the alarm signals and activates the outputs to existing sprinkler systems (Also as a part of system integration). The fire and gas detection system status is available on the control panel, OIS & also on the existing DCS systems.

Operator Interface Station

The main function of the Eagle Operator Interface Station is to display a variety of system status information. Custom graphic screens are created to display events, real-time status of all events that are currently active, gateway information, and programmable device information.


Key Features:

  • Accommodates Fire and Gas Detectors and third-party devices with 4-20 mA or "dry contact" type outputs.
  • Accommodates Deluge, Pre-Action, and Gaseous fire suppression agent release.
  • Accommodates Audible/Visual alarm devices.
  • Fault tolerant communication loop, 32,500 feet (10,000 meters) of wiring on each network.
  • Software adjustable alarm setpoints.
  • Non-volatile memory for alarm and calibration logging.
  • Built in system diagnostics.
  • Critical alarm response in 1 to 5 seconds.
  • Programmable Fire and Gas logic.
  • Modbus RTU Master/Slave and Allen Bradley DF1 communication capability through two electrically isolated RS-232 serial ports.
  • A combination, Fire & Gas Alarm and Shutdown System, as defined by NFPA-72
  • FM Approved as Local Fire Alarm System (NFPA 72)
  • FM Approved for gas detection (6310-6320)
  • CSA Approved to C22.2 No. 205 (Fire Detection)
  • CSA Approved to C22.2 No. 152 (Gas Detection)
  • CE Marked for EMI / RFI
  • CENELEC Hazardous Location Rating for field devices
  • Up to 244 intelligent network devices, fire, gas, etc., fully field addressable 500 ms. throughput from detection to shutdown
  • Class A Style "Signaling Line Circuit" (SLC) network, as defined by NFPA-72, up to 10,000 meters in length
  • Utilizing state of the art field bus technology
  • All field devices: Class 1, Division 1, Groups B, C and D
  • Comprehensive data acquisition
  • Non-volatile memory for local storage of alarm and calibration data
  • Fault tolerant communication loop
  • Built-in comprehensive diagnostics, down to the "node" level
  • Sophisticated logic capabilities and easy to use software
  • Intelligent IDC modules for contact inputs
  • Unitized UV and UV/IR Flame detectors with integral communication capabilities
  • Intelligent ARM modules for LON based releasing outputs
  • Intelligent SAM modules for LON based outputs
  • Sensor sensitivity trending

Codes & Standards

The installed system conforms to the following standards, codes and recommended practices.

Application

The Det-Tronics Eagle Quantum is a state-of-the-art Fire & Gas System consisting of any combination of addressable flame, gas, environmental detectors, and any other devices with 4-20 mA or contact outputs. The Eagle Quantum system communicates to operator stations or other host devices through two isolated RS232 serial ports utilizing Modbus RTU or Allen-Bradley DF1 protocols to make the system's data available to a variety of host devices. The information made available to host devices includes comprehensive diagnostic information on each field device along with their input and output status.

For detailed specifications on Detronics product visit website www.detronics.com